coolers

  

    Method of industrial closed loop water chiller operation is simple: the water is cooling the machine by giving up the heat in a chiller tank and returns to the machine at a set output temperature. A chiller tank includes an agitator which provides fast and uniform heat exchange between water and the evaporator. The process is controlled by a thermostat switching the refrigeration unit off at a set temperature and switching it on again, when the temperature rises. It provides a constant temperature of chilled water. Set temperature can be read at the thermostat display.


quality

    For our industrial chillers we use compressors made by the leading manufacturers (hermetic or semi-hermetic type). All components and accessories meet regulations for refrigerating devices in accordance with UW VGB 20 and for electric devices in accordance with VDE (German standards). Closed loop guarantees invariable water quality; it is not affected by impurities and scale, and the flow is unrestricted.


efficiency

    The chiller pays for itself in a short time due to:
  • Reduction of material use.
  • Improvement of quality and production output.
  • Reduction of water and waste water costs.
  • Use of recovered heat for heating purposes.

Service

    The chillers are covered by a warranty and post-warranty service.

Type IK-V 0,7 IK-V 1,4 IK-V 2 IK-V 3 IK-V 5 IK-V 7 IK-V 9 IK-V 13
Rated power kcal/h 750 1400 2000 3200 5200 7800 9750 13000
Rated power Watt 900 1630 2330 3720 6050 9070 11340 15080
Rated power kJ/h 3140 5866 8380 13408 21788 32682 50852 54470
Noise level at 3m dB 70 70 70 70 70 72 72 75
Noise level at 10m dB 62 62 62 62 62 64 64 70
Pump type NPY-2051 NPY-2051 CH 2-30 CH 2-30 CH 2-30 CH 2-50 CH 2-50 CH 4-60
Water tank l 6 40 87 87 87 140 140 300
Connector Ø6-9 Ø6-9 R 3/4" R 3/4" R 3/4" R 3/4" R 3/4" R 1"
Air consumption m3/h 600 1000 1000 2600 2750 4000 4000 8000
Compressor power kW 0,42 0,55 0,55 1,1 1,5 2,2 3 3,7
Pump power kW 0,25 0,25 0,46 0,46 0,46 0,69 0,69 1,36
Power input kW 0,67 0,83 1,13 1,68 2,08 3,1 3,9 5,53
Power supply V 1x230 1x230 1x230 3x400 3x400 3x400 3x400 3x400
Dimension mm length: 565 1000 730 730 730 860 860 1470
width: 440 440 675 675 675 760 760 730
height: 345 500 1165 1165 1165 1370 1370 1560
Weight kg 42 85 148 152 165 205 220 420

Type IK-V 18 IK-V 23 IK-V 28 IK-V 34 IK-V 40 IK-V 50 IK-V 60 IK-V 70
Rated power kcal/h 18000 23800 28000 34000 40000 50000 60000 70000
Rated power Watt 20940 27680 32560 39500 46500 58200 70000 81500
Rated power kJ/h 75420 99722 117000 142000 167500 209500 251400 293300
Noise level at 3m dB 75 75 75 75 82 82 82 82
Noise level at 10m dB 69 69 69 69 80 80 80 80
Pump type CH 4-60 CH 4-60 CHI 12-2,0 CHI 12-2,0 CHI 12-3,0 CHI 12-3,0 CHI 12-3,0 CHI 12-3,0
Water tank l 300 500 500 300/500 300/500 300 300 300
Connector R 1" R 1" R1 1/4" R1 1/4" R1 1/2" R1 1/2" R1 1/2" R1 1/2"
Air consumption m3/h 8700 13000 13000 13200 18000 20700 35000 34000
Compressor power kW 6,6 7,5 8,8 9,2/11,00 12,5/15,2 19 24 27
Pump power kW 1,36 1,36 2,26 2,26 3,35 3,35 3,35 3,35
Power input kW 8,43 9,41 11,61 13,5/15,4 18,8/21,5 24,6 31,15 33
Power supply V 3x400 3x400 3x400 3x400 3x400 3x400 3x400 3x400
Dimensions mm length: 1470 1670 1670 1800 1800 1800 3250 3250
width: 1560 1790 1790 1800 1800 1800 2150 2150
height: 1560 1790 1790 1800 1800 1800 2150 2150
Weight kg 465 540 620 780 850 1100 1300 1600



























refrigerators and freezers


    We offer non-standard refrigerators and freezers. We fill custom orders based on a provided specification or a design prepared as per Client requirements and suggestions. It addresses all Client requirements. We offer wide range of materials - sheet, wood, glass, plastic etc. All our products are covered by a warranty and post-warranty service.


          

non-standard cooling devices


    Our long-standing experience enables us to offer non-standard cooling and air conditioning systems. If use of standard systems is limited (e.g. due to low cooling efficiency or evaporation temperature of a refrigerant), we offer custom, professional systems for specific purposes. The system may include a single device or a whole batch of devices. All products are covered by a warranty and post-warranty service.



 